C7.1 Diesel Generator Rear Right
C7.1 Diesel Generator Rear Left
C7.1 Diesel Generator Front Right
C7.1 Diesel Generator Front Left
Enclosure
Enclosure
Diesel generator sets

C7.1 (60 Hz)

Producing reliable power from 120 to 175 ekW at 60 Hz, our C7.1 diesel generator sets designed to ISO 8528-5 transient response requirement. All C7.1 generator sets are available with a choice of emissions levels.

  • Maximum Rating175 ekW
  • Minimum Rating120 ekW
  • Emissions/Fuel StrategyNon Regulated
  • Voltage208 to 480 Volts
  • Frequency60 Hz
  • Duty CycleStandby, Prime
Have questions about this product?
Request a Quote
Generator Set Specifications
Maximum Rating 175 ekW
Minimum Rating 120 ekW
Emissions/Fuel Strategy Non Regulated
Voltage 208 to 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Prime
Engine Specifications
Engine Model C7.1 I-6, 4-Cycle Diesel
Bore 4.13 in
Stroke 5.31 in
Displacement 427.8 in³
Compression Ratio 16.5:1
Aspiration Turbocharged, Air to Air Aftercooled
Fuel System Common Rail
Governor Type ADEM™A4
Generator Set Dimensions
Length - Maximum 98.4 in
Width - Maximum 52 in
Height - Maximum 64 in

Control Panels

  • EMCP 4.1

Air Inlet System

  • Air cleaner; light duty with disposable element

Cooling System

  • Radiator and cooling fan with guards
  • Coolant drain line with valves
  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive

Exhaust System

  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose

Fuel System

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied

Lube System

  • Lubricating oil
  • Oil drain line with valve

Generator and Generator Attachments

  • Segregated low voltage (AC/DC) wiring panel
  • Tower panel, IP22, bottom cable entry
  • 12 Leads
  • Voltage regulator (single phase sensing)
  • IP23 Protection
  • Circuit breaker, IEC, 3 pole, mounted in tower panel

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Termination points for coolant and lube oil drain lines
  • Includes lifting provision and drag points

Packaged Generator Set <!-- I am trying out a new format to facilitate the MSS sheet/ fmh C7.1 -->

  • Radiator and cooling fan complete with protective guards
  • Flexible fuel lines to base NPT connections
  • Drip proof generator air intake (NEMA 2, IP23)
  • Class H insulation
  • Standard ambient temperatures up to 50°C (122°F)

Starting / Charging System

  • 24V battery with rack and cables

Governing System

  • Mechanical and electrical governing system - model dependent

General

  • Engine and alternator pre-paint, Caterpillar yellow
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • DE150E0 50 Hz 150.0 kVA, 60 Hz, 165.0 ekW, LC-Frame, Low BSFC Compliant Spec Sheet
    application/pdf
    Download ↓
  • DE165E0 50 Hz 165.0 kVA, 60 Hz, 187.5 ekW, LC-Frame, Low BSFC Compliant Spec Sheet
    application/pdf
    Download ↓
  • DE200E0 50 Hz 200.0 kVA, 60 Hz, 218.8 ekW, LC-Frame, Low BSFC Compliant Spec Sheet
    application/pdf
    Download ↓
  • 24-220 KVA Level 2 SA Enclosure
    application/pdf
    Download ↓
  • C7.1 Level 1 SA Enclosures 30-220 kVA (50 and 60 Hz)
    application/pdf
    Download ↓
Need installed dimensions with enclosure and tank? See Model Configurations