C13 Diesel Generator Rear Right
C13 Diesel Generator Rear Left
C13 Diesel Generator Front Right
C13 Diesel Generator Front Left
Enclosure
Enclosure
Diesel generator sets

C13 (50 Hz)

The C13 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 350 to 450 kVA at 50 Hz, our C13 diesel generator sets designed to ISO 8528-5 transient response requirements. These generator sets range from low fuel consumption systems EU Stage IIIA Non-road Emission Standards Emissions / Fuel Strategy.

  • Maximum Rating450 kVA
  • Minimum Rating350 kVA
  • Emissions/Fuel StrategyLow Fuel, R96/EUIIIa
  • Voltage380 to 415 Volts
  • Frequency50 Hz
  • Duty CycleStandby, Prime
Have questions about this product?
Request a Quote
Generator Set Specifications
Maximum Rating 450 kVA
Minimum Rating 350 kVA
Emissions/Fuel Strategy Low Fuel, R96/EUIIIa
Voltage 380 to 415 Volts
Frequency 50 Hz
Speed 1500 rpm
Duty Cycle Standby, Prime
Engine Specifications
Engine Model C13 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore 5.12 in
Stroke 6.18 in
Displacement 762.8 in³
Compression Ratio 16.3:1
Aspiration Air to Air Aftercooled
Fuel System MEUI
Governor Type Adem™A4
Generator Set Dimensions
Length - Maximum 186.7 in
Width - Maximum 79.3 in
Height - Maximum 84 in

Air Inlet System

  • Turbocharger
  • Aftercooler core
  • Air cleaner; light duty with disposable paper filter

Control Panel

  • GCCP 1.3

Cooling System

  • Radiator and cooling fan with guard
  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive
  • Coolant drain line with valve

Exhaust System

  • Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose

Fuel System

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied

Generator and Attachments

  • Power center, IP22
  • Segregated low voltage (AC/DC) wiring panel
  • Optional LC Frame generator - IP23 Protection
  • Integrated voltage regulator (IVR)
  • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
  • A Frame generator - IP21 Protection

Packaged Generator Set

  • Coolant drain line with valve
  • Disposable air filter
  • Coolant level sight gauge
  • Low coolant level sensor
  • Radiator package mounted
  • Service indicator

Governing System

  • Cat electronic governor (ADEM A4)

Lube System

  • Oil drain valves
  • Lubricating oil
  • Oil cooler

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant and lube oil drain lines

Starting / Charging System

  • 24V battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar yellow
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • DE400E0 50 Hz 400 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE450E0 50 Hz 450 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE400SE0 50 Hz 500 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE450E3 50 Hz 450 kVA, EU III Certified Emissions Spec Sheet
    application/pdf
    Download ↓
Need installed dimensions with enclosure and tank? See Model Configurations