C1.5 Generator Set Rear Right
C1.5 Generator Set Rear Left
C1.5 Generator Set Front Right
C1.5 Generator Set Front Left
Enclosure
Enclosure
Diesel generator sets

C1.5 (60 Hz)

Producing reliable power from 12 to 13.2 ekW at 60 Hz, our C1.5 diesel generator sets designed to ISO 8528-5 transient response requirements. All C1.5 generator sets are R96/EUIIIa equivalent emissions compliant.

  • Maximum Rating13.2 ekW
  • Minimum Rating12.0 ekW
  • Emissions/Fuel StrategyR96/EUIIIa Equivalent
  • Voltage110 to 415 Volts
  • Frequency60 Hz
  • Duty CycleStandby, Prime
Have questions about this product?
Request a Quote
Generator Set Specifications
Maximum Rating 13.2 ekW
Minimum Rating 12.0 ekW
Emissions/Fuel Strategy R96/EUIIIa Equivalent
Voltage 110 to 415 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Prime
Engine Specifications
Engine Model Cat® C1.5
Bore 3.3 in
Stroke 3.5 in
Displacement 91.3 in³
Compression Ratio 22.5:1
Aspiration Naturally Aspirated
Fuel System Indirect Injection
Governor Type Mechanical
Generator Set Dimensions
Length - Maximum 55.1 in
Width - Maximum 24.4 in
Height - Maximum 41.5 in

Air Inlet System

  • Air cleaner; light duty with disposable element

Control Panel

  • GCCP 1.3

Cooling System

  • Radiator and cooling fan with guards
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant

Exhaust System

  • Stub pipe, gaskets, raincap & SAE exhaust flange for customer use - shipped loose

Fuel System

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied

Generators and Generator Attachments

  • Voltage regulator (single phase sensing)
  • IP23 Protection
  • Segregated low voltage (AC/DC) wiring panel
  • Tower panel, IP22, bottom cable entry
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • 12 Leads

Governing System

  • Mechanical governing system

Lube System

  • Oil drain line with valve
  • Lubricating oil

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • includes lifting provisions and termination points for coolant

Starting / Charging System

  • 12 Volt battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar yellow
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • DE11E3S 50 Hz 11.0 kVA, 60 Hz 13.0 kVA, M Frame, EU IIIA Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE13.5E3 50 Hz 13,5 kVA, 60 Hz 16.5 kVA, M Frame, EU IIIA Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE11E3S 50 Hz 11.0 kVA, 60 Hz 13.0 kVA, LC Frame, EU IIIA Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE13.5E3 50 Hz 13.5 kVA, 60 Hz 16.5 kVA, LC Frame, EU IIIA Emissions Compliant Spec Sheet
    application/pdf
    Download ↓
  • C1C2 Diesel Generator Set, 6.8 - 22 kVA, 50/60 Hz Spec Sheet
    application/pdf
    Download ↓
  • C1C2 Diesel Generator Set, 6.8 - 22 kVA, 50/60 Hz Spec Sheet
    application/pdf
    Download ↓
Need installed dimensions with enclosure and tank? See Model Configurations