3616 Upgradeable Packaging Generator Set (Rear Right)
3616 Upgradeable Packaging Generator Set (Rear Left)
3616 Upgradeable Packaging Generator Set (Front Left)
3616 Upgradeable Packaging Generator Set (Front Left)
Diesel generator sets

3516 (60 Hz) with Upgradeable Package

Producing reliable power from 1450 to 1750 ekW at 60 Hz, our 3516 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. Generator sets offer both low fuel consumption and low emission systems.

  • Emissions/Fuel StrategyLow Fuel Consumption
  • Voltage380 to 480 Volts
  • Frequency60 Hz
  • Duty CycleStandby, Mission Critical, Prime, Continuous
  • Maximum Rating1750 ekW
  • Minimum Rating1450 ekW
Have questions about this product?
Request a Quote
Generator Set Specifications
Standby Rating 1750 ekW
Prime Power Rating 1600 ekW
Emissions/Fuel Strategy Low Fuel Consumption
Voltage 380 to 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Mission Critical, Prime, Continuous
Maximum Rating 1750 ekW
Minimum Rating 1450 ekW
Engine Specifications
Engine Model 3516 TA, V-16, 4-Stroke Water-Cooled Diesel
Bore 6.69 in
Stroke 7.48 in
Displacement 4210.64 in³
Compression Ratio 13.5:1
Aspiration TA
Fuel System Mechanical unit injection
Governor Type Woodward
Generator Set Dimensions
Length - Maximum 234.4 in
Width - Maximum 90 in
Height - Maximum 94.9 in
Dry Weight - Genset (maximum) 28840 lb

Air Inlet System

  • Air cleaner; single element canister type

Control System

  • Auto/start/stop control
  • Engine cycle crank
  • Generator set packages include Caterpillar's voltage regulator
  • Speed adjust
  • IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min / max exciter. Limiter and exciter diode monitor
  • 24 Volt DC operation
  • Engine cool-down timer
  • Text alarm/event descriptions
  • Emergency stop pushbutton
  • Environmental sealed front face
  • EMCP 4.2B
  • Generator mounted - rear facing
  • Controls:
  • Lamp test
  • Alarm acknowledge
  • PLC functionality
  • Load histogram feature
  • Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
  • ATAAC - 3516E package radiators shipped installed
  • 3 Analog inputs
  • 1 programmable digital outputs
  • Accessory module data link
  • 1 programmable relay outputs (Form C)
  • Customer data link (Modbus RTU)
  • Serial annunciator module data link
  • Cat connect
  • Digital indication for:
  • Reverse reactive power (kVAr) (32RV)
  • Number of I/O varies on options selected
  • Certified standard PGS provided
  • 6 Customer programmable digital inputs
  • RPM
  • 4 programmable relay outputs (Form A)
  • Communications:
  • Operating hours
  • Overcurrent (50/51)
  • Volts (L-L & L-N)
  • Frequency (Hz)
  • Oil pressure (psi, kPa or bar) - Coolant temperature - Volts (L-L & L-N) - Frequency (Hz) - Amps (per phase & average) - Power factor (per phase & average) - kW (per phase, average & percent) - kVA (per phase, average & percent) - kVAr (per phase, average & percent) - kW-hr (total) - kVAr-hr (total)
  • Coolant temperature
  • kVAr (per phase, average & percent)
  • kVA (per phase, average & percent)
  • Amps (per phase & average)
  • kW (per phase, average & percent)
  • Power factor (per phase & average)
  • kW-hr (total)
  • kVAr-hr (total)
  • Warning/shutdown with common LED indication of shutdowns for:
  • Emergency stop
  • Failure to start (overcrank)
  • High coolant temperature
  • Low oil pressure
  • Overspeed
  • Programmable protective relaying functions
  • Low coolant level
  • Low coolant temperature
  • Over/under voltage (27/59)
  • Generator phase sequence
  • Over/under frequency (81 o/u)
  • Reverse power (kW) (32)

Governing System

  • ADEM A3

Exhaust System

  • Flanged faced outlet(s)
  • Dry exhaust manifold

Fuel System

  • Fuel priming pump
  • Flexible fuel lines - shipped loose
  • Fuel cooler; not included with packages without radiator
  • Secondary fuel filters

General

  • Caterpillar yellow with high gloss black rails and radiator
  • SAE standard rotation
  • Right hand servicing
  • Flywheel and flywheel housing - SAE No. 00

Generator and Attachments

  • Winding temperature detectorsle pattern
  • Busbar connections, right side extension box, bottom cable entry
  • Busbar connections, top center mounted, top cable entry
  • Winding temperature detectors
  • High voltage:
  • Form wound
  • Random wound
  • Busbar connections, top center mounted, top cable entry
  • Permanent magnet excitation (PMG)
  • NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
  • Anti-condensation space heater
  • NEMA standard hole pattern
  • Permanent magnet excitation (PMG)
  • Form wound
  • Winding temperature detectors
  • 3 Phase brushless, Salient pole
  • Six lead
  • Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
  • Low voltage:
  • Internal excitation (IE)
  • Medium voltage:
  • NEMA standard hole pattern
  • NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby

Literature

  • Parts book
  • Operation & Maintenance Manual

Lubrication System

  • Oil filter, filler and dipstick
  • Oil drain lines and valve
  • Lubricating oil
  • Gear type lube oil pump
  • Integral lube oil cool
  • Fumes disposal

Mounting System

  • Rubber anti-vibration mounts - shipped loose
  • Rails - Engine/generator/radiator mounting
  • Anti-vibration mounts (shipped loose)

Starting System

  • Battery disconnect switch
  • 24 Volt electric starting motor
  • Battery and battery rack w/cables
  • 45 Amp Charging alternator
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • 3516, 60 Hz, 1750 ekW Standby/MC, 1600 ekW Prime, 1450 ekW Cont., Low Fuel Consumption Spec Sheet
    application/pdf
    Download ↓
  • 3516, 60 Hz, 1600 ekW, Prime-DCP, Low Fuel Consumption Spec Sheet
    application/pdf
    Download ↓
Need installed dimensions with enclosure and tank? See Model Configurations