Cat® Service Entrance Rated (SER) automatic transfer switches (ATS) are designed to provide standby power emergency power to entire installation loads to protect against utility power interruption; yet allow the ATS to be as close as possible to the point of service entrance. By safely and in code compliance, integrating the necessary overcurrent protection and service disconnecting means into the automatic transfer switch, a single installation can be made at the service entrance. This design eliminates the need for a separate upstream fault protection and respective interconnections, which in turn reduces installation space, time, and cost. Breaker-based Service Entrance Rated transfer switches are available from 30A to 5000A.
Draw-out type breakers (available on Power Breaker ratings) UL 891 for 4000-5000A
Lugs are 90°C rated and all control wire is #16 AWG, type XLPE with a 125°C temperature rating.
The hinges have removable hinge pins to facilitate door removal and are supplied with pad-lockable latches.
| Rating Range | 30-5000A |
|---|---|
| Transfer Type | Open / Closed / Delayed |
| Switch Type | Molded Case and Power Breaker |
| MCCB | 30-1000A 2, 3, or 4 Pole |
|---|---|
| Fixed Mount Power Breaker | 200-3200A 2, 3, 4-Pole |
| Drawout Power Breaker | 200-5000A 2, 3, or 4-Pole |
| System Voltage Application | 120-600 Vac 50/60 Hz |
| Withstand | (Power Breaker) Up to 100 kAIC at 600V 3 cycles |
| Applicable Testing | <CSA C22.2 No. 178 certified UL 1008 listed up to 3200A4000A, and 5000A UL 891 listed |
Need installed dimensions with enclosure and tank? See Model Configurations