Electric power controls

ATC-900 CONTROLLER

The ATC-900 Controller is a programmable microprocessor-based monitoring device for use on Cat transfer switches. Data access and programming operations are performed using the ATC-900's touch sensitive function buttons in conjunction with an easy-to-read illuminated alphanumeric LED display. Both the functional buttons and the display window are part of the device's door mounted front panel. A built in Help button provides user assistance in the form of message displays.

The communication option permits monitoring and control of several transfer switches, locally or remotely from a single point. Depending on the application, the user can customize the ATC-900 to meet the particular application. The ATC-900 is equipped to display historical information either via the front panel or over mod bus communications to a personal computer. Source 1 and Source 2 run time, available time and connect time are available, as well as load energized time, number of transfers, date, time and reason for the last 16 transfers.

Request a Quote
Have questions? Call 800.768.4200
Technical Summary
Rating Range120 to 600V, single phase and three phase @ 50/60 Hz
Transfer TypeSwitch application dependent
Switch TypeSwitch application dependent
ATC Controller Specifications
Input Control Voltage120Vac (50/60 Hz) (operating range 65 to 160 Vac)
Voltage Measurements of UtilitySource 1, Source 2 and Load<br>(VAB, VBC, VCA for Three Phase System)
Voltage Measurement Range0 to 700 Vac
Voltage Measurement Accuracy+/-1% of full scale
Frequency Measurements OfSource 1 and Source 2
Frequency Measurement Range40 Hz to 80 Hz
Frequency Measurement Accuracy+/- 0.1 Hz
Undervoltage DropoutBreaker Style 50 to 97% of Nominal System Voltage<br>Contactor Style - 78 to 97%
Undervoltage Pickup(Dropout +2%) to 99% of Nominal System Voltage
Underfrequency Dropout Range90 to 97% of Nominal System Frequency
Underfrequency Pickup Range(Dropout +1 Hz) to 99% of Nominal System Frequency
Overfrequency Dropout Range103 to 110% of Nominal System Frequency
Overfrequency Pickup Range101% to (Dropout +1 Hz) of nominal system frequency
Operating Temperature Range-20 to 70 degree C (-4 to +158 degree F)
Operating HumidityUp to 90% Relative Humidity (non-condensing)
Enclosure Compatibility<li>NEMA 12 (std mounting)</li><lNEMA 4/4X</li><li>NEMA 3R</li><li>UV Resistant Faceplate</li>
Ratings
System Voltage Application120 to 600 Vac (50/60 Hz) (single or three phase)

Need installed dimensions with enclosure and tank? See Model Configurations