The D600 GC (60 Hz)diesel generator sets were developed to meet your needs in a standby application. Producing reliable power of 600 ekW at 60 Hz, meeting ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. Our D600 GC generator sets meet EPA Stationary Emergency (Tier 2) certified emissions requirements.

Request a Quote
Have questions? Call 800.768.4200
Generator Set Specifications
Standby Rating600 ekW
Frequency60 Hz
Emissions/Fuel StrategyU.S. EPA Tier 2 Certified
Voltage480 to 600 Volts
Speed1800 rpm
Duty CycleStandby
Engine Specifications
Engine ModelCat® C18 In-line 6, 4-cycle Diesel
Bore5.7 in
Stroke7.2 in
Displacement1106 in³
Compression Ratio14.5:1
AspirationTurbocharged Air-to-Air Aftercooled
Fuel SystemMEUI
Governor TypeADEM™A4
Generator Set Dimensions
Length - Maximum196.1 in
Width - Maximum73.4 in
Height - Minimum79.1 in
Height - Maximum100.9 in
Dry Weight - Genset (minimum)8959.6 lb
Dry Weight - Genset (maximum)11647 lb

Air Inlet System

  • Turbocharger
  • Air cleaner - Non canister, disposable
  • Aftercooler core

Control Panel

  • GCCP 1.2

Cooling System

  • Radiator sight gauge
  • Thermostats and housing
  • Coolant drain valve
  • Jacket water pump, gear driven, centrifugal
  • Blower fan and fan drive with guards
  • Radiator, package mounted

Exhaust System

  • Exhaust manifold - dry

Fuel System

  • Fuel cooler
  • Primary fuel filter w/integral water separator and secondary filter, spin on
  • Integral tank base, 24 hours, UL142
  • Engine fuel transfer pump
  • Fuel priming pump

Generator Set

  • Complete system designed & built at ISO 9001:2000 certified facilities
  • Factory tested to design specifications at full load conditions
  • All protective devices and control functions simulated and checked

Generators and Generator Attachments

  • 6 Leads
  • Voltage regulator (single phase sensing)
  • Easy access to AVR and terminals
  • Insulation system, Class H
  • Brushless, self-excited 2/3 pitch (600V uses Internal excitation (IE))
  • Terminal box, IP22 RHS facing, bottom cable entry
  • Standard winding protection for non-harsh environments with relative humidity ? 95%
  • IP23 Protection

Governing System

  • Cat electronic governor (ADEM A4)

Lube System

  • Oil filler and dipstick
  • Shallow oil pan
  • Oil filter, spin on
  • Oil cooler
  • Lubricating oil, CK-4 (10W-30)
  • Oil drain with valve
  • Fumes disposal to front of radiator

Mounting System

  • Includes lifting provisions and termination points for coolant and lube oil drain lines
  • Captive linear vibration isolators between base and engine-generator

Protection

  • Safety shutoff - High water temperature
  • Safety shutoff - Overspeed
  • Safety shutoff - Low oil pressure

Starting/Charging System

  • 24V, 45 Amp Charging alternator
  • 24-volt electric starting motor

General

  • Parts book
  • Vibration damper
  • Lifting eyes
  • Electric Power Ratings Guide