The D400 GC diesel generator sets have been developed to meet your needs in standby applications. Producing reliable power of 400 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. Our D400 GC generator sets are engineered to EPA Stationary Emergency (Tier 3) emissions standards.
| Standby Rating | 400 ekW |
|---|---|
| Frequency | 60 Hz |
| Emissions/Fuel Strategy | U.S. EPA Tier 3 Certified |
| Voltage | 480 to 600 Volts |
| Speed | 1800 rpm |
| Duty Cycle | Standby |
| Engine Model | Cat® C13 In-line 6, 4-cycle diesel |
|---|---|
| Bore | 5.1 in |
| Stroke | 6.2 in |
| Displacement | 763 in³ |
| Compression Ratio | 16.3:1 |
| Aspiration | Turbocharged Air-to-Air Aftercooled |
| Fuel System | MEUI |
| Governor Type | ADEM™A4 |
| Length - Maximum | 182.8 in |
|---|---|
| Width - Maximum | 64.2 in |
| Height - Minimum | 80.3 in |
| Height - Maximum | 96.7 in |
| Dry Weight - Genset (minimum) | 7330.4 lb |
| Dry Weight - Genset (maximum) | 4107 lb |
Need installed dimensions with enclosure and tank? See Model Configurations