D200 GC Open Set
D200 GC Open Set
D200 GC Open Set
D200 GC Open Set
Enclosure
Enclosure
Diesel generator sets

D200 GC

Producing reliable power of 200 ekW at 60 Hz, our D200 GC diesel generator set is designed to meet ISO 8528-5 transient response requirements.

Request a Quote
Have questions? Call 800.768.4200

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

M-Frame Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

GCCP 1.2 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • UL 2200 Listed
  • ULC Certification Available

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Saves up to 18% Installed Space

Requires less space for installation; leaves more room for your on-going operations

Reliability tested for 500 Hours

Ensures you can count on emergency power when it is needed

Spare Parts 98% Fulfillment within 24 hours

World's best product support network ensures spare parts are readily available for maintenance and service needs

Generator Set Specifications
Standby Rating200 ekW
Frequency60 Hz
Emissions/Fuel StrategyU.S. EPA Tier 3 Certified
Voltage208 to 600 Volts
Speed1800 rpm
Duty CycleStandby
Engine Specifications
Engine ModelC7.1 I-6, 4-Cycle Diesel
Bore4.1 in
Stroke5.31 in
Displacement428 in³
Compression Ratio16.7:1
AspirationTurbocharged, Air to Air Aftercooled
Fuel SystemElectronic, Common Rail
Governor TypeADEM™A4
Generator Set Dimensions
Length - Maximum103.7 in
Width - Maximum51.2 in
Height - Maximum58.7 in
Dry Weight - Genset (maximum)3917 lb

Air Inlet System

  • Air cleaner; light duty with disposable element

Control Panels

  • GCCP 1.2 Control panel

Cooling System

  • Coolant drain line with valves
  • Radiator and cooling fan with guards
  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive

Generator and Generator Attachments

  • Segregated low voltage (AC/DC) wiring panel
  • Voltage regulator (single phase sensing)
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • Tower panel, IP22, bottom cable entry
  • 12 Leads
  • IP23 Protection

Exhaust System

  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose

Fuel System

  • Standard open set fuel tank/base supplied
  • Base, formed steel with single wall integral 24-hour fuel tank

Lube System

  • Oil drain line with valve
  • Lubricating oil

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provision and drag points
  • Termination points for coolant and lube oil drain lines

Starting / Charging System

  • 24V battery with rack and cables

Governing System

  • Mechanical and electrical governing system - model dependent

General

  • Engine and alternator pre-paint, Caterpillar yellow
  • Electric Power Ratings Guide
    application/pdf
  • D200 GC, C7.1, 60 Hz, 200 ekW, EPA Tier III Compliant Spec Sheet
    application/pdf
  • Cat® GC Generator Set Brochure for North America
    application/pdf

Need installed dimensions with enclosure and tank? See Model Configurations