C9 (60 Hz)

Producing reliable power from 180 to 300 ekW at 60 Hz, our C9 diesel generator sets designed to ISO 8528-5 transient response requirements. All C9 generator sets are engineered to EPA Stationary Emergency (Tier 3) emissions standards.

Request a Quote
Have questions? Call 800.768.4200
Generator Set Specifications
Standby Rating200/250/300 ekW
Prime Power Rating180/225/275 ekW
Emissions/Fuel StrategyU.S. EPA Tier 3 Certified
Voltage220 to 480 Volts
Frequency60 Hz
Speed1800 rpm
Duty CycleStandby, Prime
Engine Specifications
Engine ModelC9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore4.41 in
Stroke5.87 in
Displacement537.01 in³
Compression Ratio16.1:1
AspirationAir to Air Aftercooled
Fuel SystemHydraulic electronic unit injection
Governor TypeAdem™A4
Generator Set Dimensions
Length - Maximum157 in
Width - Maximum47.5 in
Height - Maximum73.5 in

Air Inlet System

  • Turbocharger
  • Air cleaner, light duty with disposable paper filter
  • Aftercooler core

Exhaust System

  • Exhaust manifold - dry
  • Stainless steel exhaust flex, gaskets, rain cap & SAE exhaust flange for customer use - shipped loose

Control Panels

  • GCCP 1.3

Cooling System

  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive
  • Coolant drain line with valve
  • Radiator and cooling fan with guard

Fuel System

  • Standard open set fuel tank/base supplied
  • Fuel cooler
  • Primary fuel filter w/integral water separator and secondary filter
  • Base, formed steel with single wall integral 8-hour fuel tank
  • Fuel priming pump

Generators and Generator Attachments

  • Mandatory option circuit breaker, IEC, 3 pole mounted in power centre
  • IP23 Protection
  • 12 Leads
  • Segregated low voltage (AC/DC) wiring panel
  • Insulation Class H and temperature rise
  • Power centre, IP22
  • Brushless, self-excited 2/3 pitch, random wound
  • Voltage regulator (single phase sensing)

Governing System

  • Cat electronic governor (ADEM A4)

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant and lube oil drain lines

Starting / Charging System

  • 24V battery with rack and cables

General

  • Engine and alternator re-paint, Caterpillar yellow

Lube System

  • Oil cooler
  • Oil drain valves
  • Fumes disposal, piped to front of radiator
  • Lubricating oil
  • Oil filter and dipstick
  • Oil drain lines with valve; piped to edge of base
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • C9 60 Hz, 200 ekW, Tier III Non-Road Emissions Compliant Spec Sheet
    application/pdf
    Download ↓
  • C9 60 Hz, 250 ekW, Tier III Non-Road Emissions Compliant Spec Sheet
    application/pdf
    Download ↓
  • C9 60 Hz, 300 ekW, Tier III Non-Road Emissions Compliant Spec Sheet
    application/pdf
    Download ↓
  • 200 ekW - 300 ekW Spec Sheet
    application/pdf
    Download ↓
  • DE200SE0 60 Hz 250 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE250E0 60 Hz 313 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE275SE0 60 Hz 344 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE300SE0 60 Hz 375 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE300SE3 60 Hz 375 kVA, EU Stage III Emissions Compliant Spec Sheet
    application/pdf
    Download ↓
  • 200 - 300 ekW Spec Sheet
    application/pdf
    Download ↓

Need installed dimensions with enclosure and tank? See Model Configurations