Diesel generator sets

C9 (50 Hz)

Producing reliable power from 230 to 330 kVA at 50 Hz, our C9 diesel generator sets designed to ISO 8528-5 transient response requirements. All C9 generator sets are engineered to EPA Stationary Emergency (Tier 3) emissions standards.

Request a Quote
Have questions? Call 800.768.4200

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

R-Frame Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

GCCP1.3 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Generator Features

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency

Certifications

  • The generator set meets transient response and block loading steps as per ISO 8528-5.

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Integrated Cat® Product Link™ Control System

Track Genset Health and Operation ParametersGenset Utilization and Performance Tracking

Remote Connectivity 24/7/365 Monitoring

Cat Connect option ensures your generator set is always ready to start and perform as expected

Optimised for 5% Lower Fuel Consumption

Longer run times between fuel fills; reduced operating costs

Generator Set Specifications
Standby Rating250/275/300/330 kVA
Prime Power Rating230/250/275/300 kVA
Emissions/Fuel StrategyNon-Certified Emissions / EU Stage IIIA
Voltage200 to 400 Volts
Frequency50 Hz
Speed1500 rpm
Duty CycleStandby, Prime
Engine Specifications
Engine ModelC9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore4.41 in
Stroke5.87 in
Displacement537.01 in³
Compression Ratio16.1:1
AspirationAir to Air Aftercooled
Fuel SystemHydraulic electronic unit injection
Governor TypeAdem™A4
Generator Set Dimensions
Length - Maximum157 in
Width - Maximum47.5 in
Height - Maximum73.5 in

Air Inlet System

  • Air cleaner, light duty with disposable paper filter

Control Panels

  • GCCP 1.3

Cooling System

  • Fan drive, battery charging alternator drive
  • Radiator and cooling fan with guard
  • Caterpillar extended life coolant
  • Coolant drain line with valve

Exhaust System

  • Stainless steel exhaust flex, gaskets, rain cap & SAE exhaust flange for customer use - shipped loose

Fuel System

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied

Generators and Generator Attachments

  • 12 Leads
  • Mandatory option circuit breaker, IEC, 3 pole mounted in power centre
  • Voltage regulator (single phase sensing)
  • Segregated low voltage (AC/DC) wiring panel
  • IP23 Protection
  • Power centre, IP22

Governing System

  • Cat electronic governor (ADEM A4)

Lube System

  • Oil drain valves
  • Lubricating oil
  • Oil cooler

Mounting System

  • Includes lifting provisions and termination points for coolant and lube oil drain lines
  • Captive linear vibration isolators between base and engine-generator

Starting / Charging System

  • 24V battery with rack and cables

General

  • Engine and alternator re-paint, Caterpillar yellow
  • Electric Power Ratings Guide
    application/pdf
  • DE250E0 50 Hz 250 kVA, Non Certified Emissions Spec Sheet
    application/pdf
  • DE275E0 50 Hz 275 kVA, Non Certified Emissions Spec Sheet
    application/pdf
  • DE275E3 50 Hz 275 kVA, EU Stage IIIA Emissions Compliant Spec Sheet
    application/pdf
  • DE300E3 50 Hz 300 kVA, EU Stage IIIA Emissions Compliant Spec Sheet
    application/pdf
  • DE300E0 50 Hz 300 kVA, Non Certified Emissions Spec Sheet
    application/pdf
  • DE330E0 50 Hz 330 kVA, Non Certified Emissions Spec Sheet
    application/pdf
  • 250 - 330 ekW Spec Sheet
    application/pdf