C4.4 Open Set Rear Right
C4.4 Open Set Rear Left
C4.4 Open Set Front Right
C4.4 Open Set Front Left
Enclosure
Enclosure
Diesel generator sets

C4.4 (50 Hz)

Producing reliable power from 50 to 110 kVA at 50 Hz, our C4.4 diesel generator sets designed to ISO 8528-5 transient response requirements. All C4.4 to meet EPA Stationary Emergency (Tier 3) emissions standards.

Request a Quote
Have questions? Call 800.768.4200
Generator Set Specifications
Standby Rating55/65/88/90/110 kVA
Prime Power Rating50/60/80/82/100 kVA
Emissions/Fuel StrategyLow BSFC / EU Stage IIA / EU Stage IIIA
Voltage110 to 480 Volts
Frequency50 Hz
Speed1500 rpm
Duty CycleStandby, Prime
Engine Specifications
Engine ModelCat® C4.4
Bore4.1 in
Stroke5 in
Displacement268.5 in³
Compression Ratio16.2:1, 17.25:1, 18.2:1 or 18.3:1
AspirationTurbocharged
Fuel SystemDirect Injection or Common Rail
Governor TypeMechanical
Generator Set Dimensions
Length - Maximum75.8 in
Width - Maximum44.1 in
Height - Maximum53.6 in

Air Inlet System

  • Air cleaner; light duty with disposable element

Cooling System

  • Coolant drain line with valve
  • Caterpillar extended life coolant
  • Radiator and cooling fan with guards
  • Fan drive, battery charging alternator drive

Exhaust System

  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose

Fuel System

  • Standard open set fuel tank/base supplied base, formed steel with single wall integral 8-hour fuel tank

Control Panel

  • GCCP 1.3

Generators and Attachments

  • Voltage regulator (single phase sensing)
  • Tower panel, IP22, bottom cable entry
  • IP23 Protection
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • 12 Leads
  • Segregated low voltage (AC/DC) wiring panel

Governing System

  • Mechanical and electrical governing system - model dependent

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provision and drag points
  • Termination points for coolant and lube oil drain lines

Starting/Charging System

  • Batteries
  • 24V battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar yellow

Lube System

  • Oil drain line with valve
  • Lubricating oil
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • DE55E2 50 Hz 55.0 kVA, LC Frame, EU II Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE55E3S 50 Hz 55.0 kVA, LC Frame, EU IIIA Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE65E3 50 Hz 65.0 kVA, LC Frame, EU IIIA Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE88E0 50 Hz 88.0 kVA Standby, 50 Hz 100 kVA, LC Frame, Low BSFC Spec Sheet
    application/pdf
    Download ↓
  • DE88E3 50 Hz 88.0 kVA, LC Frame, EU IIIA Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE90E2S 50 Hz 90.0 kVA, LC Frame, EU II Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE90E2S 50 Hz 90.0 kVA, LC Frame, EU II Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE110E2 50 Hz 110.0 kVA Standby, 50 Hz 100.0 kVA Prime, LC Frame, EU II Compliant Spec Sheet
    application/pdf
    Download ↓
  • DE110E3, 50 Hz 110.0 kVA, LC Frame, EU IIIA Compliant Spec Sheet
    application/pdf
    Download ↓
  • DE55E2 50 Hz 55.0 kVA, M Frame, EU II Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE55E3S 50 Hz 55.0 kVA, M Frame, EU IIIA Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE65E3 50 Hz 65.0 kVA, M Frame, EU IIIA Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE88E0 50 Hz 88.0 kVA Standby, 50 Hz 80 kVA Prime, M Frame, Low BSFC Spec Sheet
    application/pdf
    Download ↓
  • DE88E3 50 Hz 88.0 kVA, M-Frame, EUIIIA Compliant Spec Sheet
    application/pdf
    Download ↓
  • DE90E2S 50 Hz 90.0 kVA Standby, 50 Hz 82.0 kVA Prime, M Frame, EU II Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE90E3S 50 Hz 90.0 kVA, M Frame, EU II Compliant Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE110E2 50 Hz 110.0 kVA, M-Frame, EUIII Compliant Spec Sheet
    application/pdf
    Download ↓
  • DE110E3 50 Hz 110.0 kVA, M-Frame, EUIIIA Compliant Spec Sheet
    application/pdf
    Download ↓

Need installed dimensions with enclosure and tank? See Model Configurations