Producing reliable power from 910 kVA to 1500 kVA at 50 Hz, our C32B diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100 % rated load in one step. Our C32B generator sets are made for demands, so you can make yours.

Request a Quote
Have questions? Call 800.768.4200
Generator Set Specifications
Standby Rating1100/1250/1400/1500 kVA
Prime Power Rating1000/1100 kVA
Emissions/Fuel StrategyLow BSFC
Voltage400 to 3300 Volts
Frequency50 Hz
Speed1500 rpm
Duty CycleStandby, Mission Critical, Prime, Continuous
Engine Specifications
Engine ModelC32B TA, V-12, 4-Stroke Water-Cooled Diesel
Bore5.71 in
Stroke6.38 in
Displacement1958.86 in³
Compression Ratio15.0:1
AspirationTA
Fuel SystemMEUI
Governor TypeAdem™A4
Generator Set Dimensions
Length - Minimum164 in
Length - Maximum176.6 in
Width - Minimum66.3 in
Width - Maximum87.8 in
Height - Minimum85.1 in
Height - Maximum86.4 in
Dry Weight - Genset (minimum)14700 lb
Dry Weight - Genset (maximum)17855 lb

Air Inlet System

  • Single element canister type with service indicator

Control Panel

  • GCCP 1.2
  • GCCP 1.3
  • Warning shutdowns
  • Control features
  • Communications
  • Programmable protective relaying functions
  • Digital indicators

Cooling System

  • Radiator fan and fan drive
  • Coolant drain line with valve
  • ATAAC
  • Caterpillar extended life coolant
  • Fan and belt guards
  • Low coolant level sensor

Exhaust

  • Exhaust manifold - dry
  • 203 mm (8 in) ID round flanged outlet

Fuel System

  • Primary fuel filter with water separator
  • Secondary fuel filters
  • Fuel cooler
  • Fuel priming pump

Generators and Attachments

  • 6 Lead
  • Salient pole
  • NEMA Class H insulation
  • Internal excitation (IE)
  • Permanent magnet excitation (PMG)
  • Reactive droop
  • 3 Phase brushless
  • Winding temperature detectors
  • Class H temperature rise at 40C ambient
  • Busbar connections, top center mounted, top cable entry
  • IEC standard hole pattern
  • Integrated voltage regulator (IVR)

Governing System

  • ADEM(tm) A4

Mounting System

  • Rubber anti-vibration mounts
  • Rails - engine/generator/radiator mounting

Lube System

  • Gear type lube oil pump
  • Oil filter, filler and dipstick
  • Integral lube Oil cooler
  • Fumes disposal
  • Oil drain lines and valve
  • Lubricating oil

Power Termination

  • Busbar

Starting / Charging System

  • Battery disconnect switch
  • Battery, rack and cables
  • 24 Volt electric starting motor
  • 45 Amp Charging alternator

General

  • Caterpillar yellow with high gloss black rails & radiator
  • Flywheel and flywheel housing-SAE
  • SAE standard rotation
  • RH service
  • Electric Power Ratings Guide
    application/pdf