C175-16 Diesel Generator Sets
C175-16 Diesel Generator Sets Front Left
C175-16 Diesel Generator Sets Front Right
C175-16 Diesel Generator Sets Rear Left
Diesel generator sets

C175-16 (50 Hz)

Producing reliable power from 2500 - 3100 kVA at 50 Hz, our 175-16 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. The generator set is optimized for Low Fuel Consumption or Low Emissions.

Request a Quote
Have questions? Call 800.768.4200
Generator Set Specifications
Standby Rating3100(no fan)/3000 kVA
Prime Power Rating2825(no fan)/2725 kVA
Emissions/Fuel StrategyLow Fuel, Low Emissions
Voltage380 to 11000 Volts
Frequency50 Hz
Speed1500 rpm
Duty CycleStandby, Mission Critical, Prime, Continuous
Maximum Rating3100 kVA
Minimum Rating2500 kVA
Engine Specifications
Engine ModelC175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel
Bore6.89 in
Stroke8.66 in
Displacement5166.88 in³
Compression Ratio16.7:1
AspirationTurbo Aftercooled
Fuel SystemCommon Rail
Governor TypeADEM� A4
Generator Set Dimensions
Length - Minimum251.9 in
Length - Maximum320.2 in
Width - Minimum82.7 in
Width - Maximum109.1 in
Height - Minimum86.9 in
Height - Maximum130.1 in
Dry Weight - Genset (minimum)42750 lb
Dry Weight - Genset (maximum)50750 lb

Air Inlet System

  • 4 x Single element canister with service indicator(s)

Control Panel

  • Cat ECS 100
  • Volts (L-L & L-N)
  • Engine cycle crank
  • Power factor (per phase & average)
  • Overcurrent
  • Communications
  • Emergency stop
  • 2 Programmable relay outputs (Form C)
  • 6 Programmable digital inputs
  • 2 Programmable digital outputs
  • Environmental sealed front face.
  • DC Volts
  • Reverse power
  • Programmable protective relaying functions
  • High coolant temperature
  • Accessory module data link
  • Low coolant level
  • Over/under frequency
  • Amps (per phase & average)
  • True RMS AC metering, 3-phase, +/-2% accuracy
  • Low coolant temperature
  • Reverse reactive power
  • Controls
  • Oil pressure (psi, kPa or bar)
  • Lamp test
  • Coolant temperature
  • Warning/shutdown Indicators:
  • 4 Programmable relay outputs (Form A)
  • Alarm acknowledge
  • Generator phase sequence
  • 24 Volt DC operation
  • Serial annunciator module data link
  • Customer data link (Modbus RTU)
  • Failure to start (overcrank)
  • Auto/start/stop control.
  • Low oil pressure
  • RPM
  • Text alarm/event descriptions.
  • Digital Indicators
  • Generator mounted - rear facing
  • Emergency stop pushbutton
  • Engine cool-down timer
  • Operating hours
  • Over/under voltage
  • Overspeed
  • Frequency (Hz)

Cooling System

  • Radiator group - shipped loose
  • SCAC cooling
  • Coolant Sensors
  • Coolant drain line and valves
  • Fan and belt guards

Exhaust System

  • Bolted flange, with bellow for each turbo
  • Dry exhaust manifold

Fuel System

  • Filters x 3
  • Secondary/ tertiary fuel filters
  • 10 Micron spin On Type
  • 4 Micron Spin On Type
  • Primary fuel filter water/fuel water separator
  • Engine mounted filters x 3

Generator and Attachments

  • 6 Leads
  • IEC platinum stator RTDs
  • Voltage regulator
  • Reactive droop capability
  • 3 Phase voltage sensing
  • RFI suppression
  • Min / max exciter limiter
  • exciter diode monitor
  • Form wound
  • Permanent magnet excitation (PMG)
  • NEMA Class H insulation
  • Class H temperature rise at 40C ambient
  • (LV) Busbar connections, top/center mounted, top cable entry
  • 3 Phase Brushless
  • Salient pole
  • 50 Hz models: IEC standard hole pattern
  • (MV) Busbar connections, right side extension box, bottom cable entry
  • Anti-condensation space heater
  • Class F temperature rise at 40C ambient
  • Right side extension box, bottom cable entry

Governing System

  • ADEM A4
  • Redundant shutdown (Overspeed protection through a duplicate speed sensing system)

Lube System

  • Gear type lube oil pump
  • Lubricating oil
  • Fumes disposal
  • Integral lube Oil cooler
  • Oil drain lines and valve
  • Oil filter, filler and dipstick
  • Prelube - required with prime, continuous, and standby

Mounting Systems

  • Rubber anti-vibration mounts - shipped loose
  • Battery disconnect switch
  • Batteries and battery rack w/cables
  • Dual 24 volt electric starting motors
  • Rails - Engine/generator

Service Instructions

  • Two PM inspections

Power Termination

  • Busbar

General

  • Paint - Caterpillar yellow with high gloss black rails & radiator
  • Right hand servicing
  • Flywheel and flywheel housing-SAE No. 00
  • SAE standard rotation
  • Electric Power Rating Guide
    application/pdf
    Download ↓
  • C175-16, 50 Hz, 3000 kVA Standby/MC, 2725 kVA Prime, 2500 kVA Cont., Low Fuel Consumption / Low Emissions (with fan) Spec Sheet
    application/pdf
    Download ↓
  • C175-16, 50 Hz, 3100 kVA Standby/MC, 2825 kVA Prime, 2600 kVA Cont., Low Fuel Consumption / Low Emissions (without fan) Spec Sheet
    application/pdf
    Download ↓
  • C175-16, 50 Hz, 2725 kVA, Prime-DCP, Low Fuel Consumption (with fan) Spec Sheet
    application/pdf
    Download ↓
  • C175-16, 50 Hz, 2825 kVA, Prime-DCP, Low Fuel Consumption (without fan) Spec Sheet
    application/pdf
    Download ↓

Need installed dimensions with enclosure and tank? See Model Configurations