C13 Diesel Generator Front Right
C13 Diesel Generator Front Left
C13 Diesel Generator Rear Right
C13 Diesel Generator Rear Left
Enclosure
Enclosure
Diesel generator sets

C13 (60 Hz)

The C13 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 320 to 400 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. Our C13 generator sets are certified to Low Fuel Consumption Emissions / Fuel Strategy.

Request a Quote
Have questions? Call 800.768.4200
Generator Set Specifications
Standby Rating350/400 ekW
Prime Power Rating320/350 ekW
Emissions/Fuel StrategyLow BSFC
Voltage380 to 415 Volts
Frequency60 Hz
Speed1800 rpm
Duty CycleStandby, Prime
Engine Specifications
Engine ModelC13 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore5.12 in
Stroke6.18 in
Displacement762.8 in³
Compression Ratio16.3:1
AspirationAir to Air Aftercooled
Fuel SystemMEUI
Governor TypeAdem™A4
Generator Set Dimensions
Length - Maximum186.7 in
Width - Maximum79.3 in
Height - Maximum84 in

Air Inlet System

  • Aftercooler core
  • Air cleaner; light duty with disposable paper filter
  • Turbocharger

Control Panel

  • GCCP 1.3

Cooling System

  • Caterpillar extended life coolant
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Radiator and cooling fan with guard

Exhaust System

  • Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose

Fuel System

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied

Generator and Attachments

  • Segregated low voltage (AC/DC) wiring panel
  • Power center, IP22
  • Integrated voltage regulator (IVR)
  • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
  • A Frame generator - IP21 Protection
  • Optional LC Frame generator - IP23 Protection

Governing System

  • Cat electronic governor (ADEM A4)

Packaged Generator Set

  • Service indicator
  • Radiator package mounted
  • Low coolant level sensor
  • Coolant drain line with valve
  • Coolant level sight gauge
  • Disposable air filter

Lube System

  • Lubricating oil
  • Oil drain valves
  • Oil cooler

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant and lube oil drain lines

Starting / Charging System

  • 24V battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar yellow
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • DE350SE0 60 Hz 438 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • DE400SE0 60 Hz 500 kVA, Non Certified Emissions Spec Sheet
    application/pdf
    Download ↓
  • C13, 350 - 400 ekW Spec Sheet
    application/pdf
    Download ↓

Need installed dimensions with enclosure and tank? See Model Configurations