Diesel generator sets

3608 (60 Hz)

Producing reliable power from 2200 to 2660 ekW at 60 Hz, our 3608 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. The generator set is certified for low fuel consumption.

Request a Quote
Have questions? Call 800.768.4200
Generator Set Specifications
Maximum Rating2660 ekW
Minimum Rating1830 ekW
Emissions/Fuel StrategyLow Fuel Consumption
Frequency60 Hz
Speed720 & 900 rpm
Duty CycleStandby, Prime, Continuous
Engine Specifications
Engine Model3608 I-8,4-Stroke Water-Cooled Diesel
Bore11 in
Stroke11.8 in
Displacement9064 in³
Compression Ratio13:01
AspirationTA
Fuel SystemDirect unit injection
Governor TypeGenerator Set Monitoring System (GMS)
Generator Set Dimensions
Length - Maximum404 in
Width - Maximum99.62 in
Height - Maximum156.6 in
Dry Weight - Genset (maximum)91050 lb

Air Inlet System <!-- 3600 series only -->

  • Aftercooler, fresh water, corrosion resistant coated (air side)
  • Air inlet shutoff
  • Turbocharger, watercooled (720 rpm and HFO), engine oil lubricated
  • Breather, crankcase, top-mounted

Cooling System

  • Engine coolant water drains
  • Water temperature regulator
  • Jacket water thermostats

Exhaust System

  • Includes adapter, flexible exhaust fitting
  • 457 mm (18 in) Cat bolt pattern
  • Dry, gas tight, exhaust manifold

Fuel System

  • Simplex or duplex

Generator System

  • Custom generator per generator data sheet completed by dealer

Governor System

  • UG Actuator

Lube System

  • Oil filler and dipstick
  • Service side engine mounted on cylinder block inspection covers
  • Wet oil sump. Includes engine-driven main lubrication and oil pumps, oil lines and oil pan
  • Centrifugal oil filters with single shutoff
  • Oil pressure regulating valve
  • Crankcase explosion relief valves

Mounting System

  • Engine and generator mounting
  • Damper, torsional vibration

Starting / Charging System

  • Air silencer
  • One motor, engine mounted at rear, on left side
  • Vane type air starter
  • Line group for single point custom connection

General:

  • Gear driven pumps: Fuel/oil/jacket water/Aftercooler/Oil cooler water
  • Paint, Caterpillar yellow
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • 3608, 60 Hz, 2660 ekW Standby, 2420 ekW Prime, 2200 ekW Cont., Low Fuel Consumption Spec Sheet
    application/pdf
    Download ↓

Need installed dimensions with enclosure and tank? See Model Configurations