DE110E2 Open Rear Right
DE110E2 Open Rear Left
DE110E2 Open Front Right
DE110E2 Open Front Left
Enclosure
Enclosure
Diesel generator sets

C4.4 | DE110E2

Producing reliable power 100 ekW at 60 Hz, our DE110E2 generator set powerd by C4.4 diesel engine designed to ISO 8528-5 transient response requirements.
DE110E2 generator sets is EUIIa equivalent emissions compliant.

Request a Quote
Have questions? Call 800.768.4200
Generator Set Specifications
Minimum Rating100 ekW
Maximum Rating100 ekW
Emissions/Fuel StrategyEU Stage II R96
Voltage240 to 480 Volts
Frequency60 Hz
Speed1800 rpm
Duty CycleStandby, Prime
Engine Specifications
Engine ModelCat® C4.4
Bore4.13 in
Stroke5 in
Displacement268.5 in
Compression Ratio18.3:1
AspirationTurbocharged
Fuel SystemInline
Governor TypeElectronic
Generator Set Dimensions
Length - Maximum82.2 in
Width - Maximum44.1 in
Height - Maximum54.1 in
Dry Weight - Genset (maximum)2490 lb

Control panel

  • EMCP 4.1 Control panel

Alternator and Alternator attachments

  • 12 Leads
  • IP23 Protection
  • Voltageregulator (single phase sensing)
  • Tower panel, IP22, bottom cable entry
  • Segregated low voltage (AC/DC) wiring panel
  • Circuit breaker, IEC, 3 Pole, mounted in tower panel

Governing system

  • Electronic governing system

Cooling system

  • Radiator and cooling fan with guards
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant

Air inlet system

  • Air cleaner; light duty with disposable element

Exhaust system

  • Stub pipe, gaskets, raincap & SAE exhaust flange
  • Industrial silencer

Fuel system

  • Standard open set fuel tank/base

Lube system

  • Lubricating oil
  • Oil drain line with valve

Mounting system

  • Captive linear vibration isolators
  • Lifting provision and drag points
  • Termination points for coolant and lube oil drain lines

Starting/charging system

  • 12V Battery with rack & cables

General

  • Engine and alternator pre-paint, Caterpillar yellow
  • Electric Power Ratings Guide
    application/pdf
    Download ↓
  • DE110E2, 60 Hz 100.0 kW, M Frame, EUII Emissions Compliant Spec Sheet
    application/pdf
    Download ↓
  • DE110E2, 60 Hz 100.0 kW, R Frame, EUII Emissions Compliant Spec Sheet
    application/pdf
    Download ↓

Need installed dimensions with enclosure and tank? See Model Configurations